Stagehand Pro 3e Parameters

Parameters - the reckoning

There are a lot of parameters - just 1 mis-set parameter can cause countless hours of troubleshooting chaos.

The Stagehand Pro 3e does not includes an external keypad to the Mitsubishi E800 series VFD. If you need to manually restore parameters, you'll need to open the top of the case to get to the keypad.

With the case open, confirm the stock parameters are set properly, making any adjustments based on the machine connected. If you've checked the parameters and are still stuck, it's time to start from scratch by resetting the VFD back to factory settings.

Once you have reset the VFD you'll need to manually input the Stock Parameters. Jump to the bottom of the page to find the proper values for each of our stock machines.

No.NameNotesInitial valueSetting value

0

Torque boost

Compensate for low torque in V/f mode

4

4

1

Maximum frequency

Max frequency output from the VFD

120

120

2

Minimum frequency

Min frequency output from the VFD

0

0

3

Base frequency

From motor nameplate

60

60

7

Acceleration time

Drive level - not used

5

0

8

Deceleration time

Drive level - not used

5

0

9

Electronic thermal O/L relay/Rated motor current

From motor nameplate

17.5

17.5

10

DC injection brake operation frequency

Hz level when the VFD will apply the DC injection braking

3

0.5

11

DC injection brake operation time

DC injection brake timing

0.5

0.5

12

DC injection brake operation voltage

Voltage applied (% of input voltage)

4

4

13

Starting frequency

VFD will not start below this value

0.5

0.5

22

Stall prevention operation level (torque limit level)

Torque limit (%)

150

200

30

Regenerative function selection

Brake resistor installed

0

1

70

Special regenerative brake duty

Based on braking resistor installed

0

10

71

Applied motor

3 = Induction motor

0

3

72

PWM frequency selection

Performance & noise

1

15

73

Analog input selection

0-5VDC

1

1

77

Parameter write selection

enabled across all states

0

2

79

Operation mode selection

External operation

0

2

80

Motor capacity

From motor nameplate

9999

3.7

81

Number of motor poles

Nameplate motor RPM 2=3500rpm, 4=1750rpm, 6=1150rpm

9999

4

83

Rated motor voltage

From motor nameplate

200

230

84

Rated motor frequency

From motor nameplate

9999

60

96

Auto tuning setting/status

0

0

117

PU communication station number

Modbus

0

1

118

PU communication speed

Modbus

192

384

119

PU communication stop bit length / data length

Modbus

1

0

120

PU communication parity check

Modbus

2

0

121

Number of PU communication retries

Modbus

1

1

122

PU communication check time interval

Modbus

0

9999

125

Terminal 2 frequency setting gain frequency

Set what 100% = in hertz (overspeed)

60

60

152

Zero current detection level

open circuit detection

5

5

153

Zero current detection time

open circuit detection

0.5

0.1

156

Stall prevention operation selection

V/f & Magnetic flux modes only

0

3

180

RL terminal function selection

I/O

0

9999

181

RM terminal function selection

I/O

1

9999

182

RH terminal function selection

I/O

2

50

183

MRS terminal function selection

I/O

24

9999

184

RES terminal function selection

I/O

62

9999

190

RUN terminal function selection

I/O

0

9999

191

FU terminal function selection

I/O

4

9999

192

ABC terminal function selection

I/O

99

199

316

D03 Output Selection

Y13 Signal: Zero current detection to PLC (keypad only)

9999

113

359

Encoder rotation direction

100 (CW) or 101 (CCW)

101

101

369

Number of encoder pulses

Motor Encoder resolution (vector mode)

1024

1024

374

Overspeed detection level

Mitsu default

9999

9999

376

Encoder signal loss detection enable/disable selection

Enabled

0

1

414

PLC function operation selection

PLC program to load

0

2

549

Protocol selection

MODBUS RTU protocol

0

1

800

Control method selection

0=Vector, 10=Sensorless Vector, 40=V/f

40

0

820

Speed control P gain 1

Drive level PID

60

20

1199

PLC function user parameter 50

open circuit detection

0

50

C4

Terminal 2 Input gain

Making sure 100% = 60Hz See the instructions on setting the C4 value.

100

Stagehand Pro 3e Machine Specific Parameters

Spotline/Pushstick/Revolver

Pr.NameSetting

9

Electronic thermal O/L relay/Rated motor current

13.5

3

Base frequency

60

71

Applied Motor

3

80

Motor Capacity (kw)

3.7

81

Motor Poles

4

83

Motor Voltage

230

84

Motor Frequency

60

125

Terminal 2 gain frequency

60

359

Motor encoder direction

101

800

Control method: 0=Vector, 10=Sensorless Vector, 20=V/f

0

CM Smart Chain Hoist

Pr.NameSetting

9

Electronic thermal O/L relay/Rated motor current

13

1

Maximum frequency

110

3

Base frequency

106

71

Applied Motor

3

80

Motor Capacity (kw)

2.63

81

Motor Poles

4

83

Motor Voltage

230

84

Motor Frequency

106

125

Terminal 2 gain frequency

106

359

Motor encoder direction

100

800

Control method: 0=Vector, 10=Sensorless Vector, 20=V/f

0

820

Speed control P gain 1

10

Floorpocket Lift

Pr.NameSetting

9

Electronic thermal O/L relay/Rated motor current

17.5

1

Maximum frequency

80

3

Base frequency

60

71

Applied Motor

3

80

Motor Capacity (kw)

3.7

81

Motor Poles

4

83

Motor Voltage

230

84

Motor Frequency

60

125

Terminal 2 gain frequency

60

800

Control method: 0=Vector, 10=Sensorless Vector, 20=V/f

0

Last updated