Stagehand Pro 3e Parameters
Parameters - the reckoning
There are a lot of parameters - just 1 mis-set parameter can cause countless hours of troubleshooting chaos.
The Stagehand Pro 3e does not includes an external keypad to the Mitsubishi E800 series VFD. If you need to manually restore parameters, you'll need to open the top of the case to get to the keypad.
With the case open, confirm the stock parameters are set properly, making any adjustments based on the machine connected. If you've checked the parameters and are still stuck, it's time to start from scratch by resetting the VFD back to factory settings.
Once you have reset the VFD you'll need to manually input the Stock Parameters. Jump to the bottom of the page to find the proper values for each of our stock machines.
No. | Name | Notes | Setting value |
---|---|---|---|
0 | Torque boost | Compensate for low torque in V/f mode | 4 |
1 | Maximum frequency | Max frequency output from the VFD | 120 |
2 | Minimum frequency | Min frequency output from the VFD | 0 |
3 | Base frequency | From motor nameplate | 60 |
7 | Acceleration time | Drive level - not used | 0 |
8 | Deceleration time | Drive level - not used | 0 |
9 | Electronic thermal O/L relay/Rated motor current | From motor nameplate | 17.5 |
10 | DC injection brake operation frequency | Hz level when the VFD will apply the DC injection braking | 0.5 |
11 | DC injection brake operation time | DC injection brake timing | 0.5 |
12 | DC injection brake operation voltage | Voltage applied (% of input voltage) | 4 |
13 | Starting frequency | VFD will not start below this value | 0.5 |
22 | Stall prevention operation level (torque limit level) | Torque limit (%) | 200 |
30 | Regenerative function selection | Brake resistor installed | 1 |
70 | Special regenerative brake duty | Based on braking resistor installed | 10 |
71 | Applied motor | 3 = Induction motor | 3 |
72 | PWM frequency selection | Performance & noise | 15 |
73 | Analog input selection | 0-5VDC | 1 |
77 | Parameter write selection | enabled across all states | 2 |
79 | Operation mode selection | External operation | 2 |
80 | Motor capacity | From motor nameplate | 3.7 |
81 | Number of motor poles | Nameplate motor RPM 2=3500rpm, 4=1750rpm, 6=1150rpm | 4 |
83 | Rated motor voltage | From motor nameplate | 230 |
84 | Rated motor frequency | From motor nameplate | 60 |
96 | Auto tuning setting/status | 0 | |
117 | PU communication station number | Modbus | 1 |
118 | PU communication speed | Modbus | 384 |
119 | PU communication stop bit length / data length | Modbus | 0 |
120 | PU communication parity check | Modbus | 0 |
121 | Number of PU communication retries | Modbus | 1 |
122 | PU communication check time interval | Modbus | 9999 |
125 | Terminal 2 frequency setting gain frequency | Set what 100% = in hertz (overspeed) | 60 |
152 | Zero current detection level | open circuit detection | 5 |
153 | Zero current detection time | open circuit detection | 0.1 |
156 | Stall prevention operation selection | V/f & Magnetic flux modes only | 3 |
180 | RL terminal function selection | I/O | 9999 |
181 | RM terminal function selection | I/O | 9999 |
182 | RH terminal function selection | I/O | 50 |
183 | MRS terminal function selection | I/O | 9999 |
184 | RES terminal function selection | I/O | 9999 |
190 | RUN terminal function selection | I/O | 9999 |
191 | FU terminal function selection | I/O | 9999 |
192 | ABC terminal function selection | I/O | 199 |
316 | D03 Output Selection | Y13 Signal: Zero current detection to PLC (keypad only) | 113 |
359 | Encoder rotation direction | 100 (CW) or 101 (CCW) | 101 |
369 | Number of encoder pulses | Motor Encoder resolution (vector mode) | 1024 |
374 | Overspeed detection level | Mitsu default | 9999 |
376 | Encoder signal loss detection enable/disable selection | Enabled | 1 |
414 | PLC function operation selection | PLC program to load | 2 |
549 | Protocol selection | MODBUS RTU protocol | 1 |
800 | Control method selection | 0=Vector, 10=Sensorless Vector, 40=V/f | 0 |
820 | Speed control P gain 1 | Drive level PID | 20 |
1199 | PLC function user parameter 50 | open circuit detection | 50 |
C3 | Terminal 2 frequency setting bias | Making 0% = 0Hz See the instructions on setting the C3 value. | |
C4 | Terminal 2 Input gain | Making sure 100% = 60Hz See the instructions on setting the C4 value. |
Stagehand Pro 3e Machine Specific Parameters
Spotline/Pushstick/Revolver
Pr. | Name | Setting |
---|---|---|
9 | Electronic thermal O/L relay/Rated motor current | 13.5 |
3 | Base frequency | 60 |
71 | Applied Motor | 3 |
80 | Motor Capacity (kw) | 3.7 |
81 | Motor Poles | 4 |
83 | Motor Voltage | 230 |
84 | Motor Frequency | 60 |
125 | Terminal 2 gain frequency | 60 |
359 | Motor encoder direction | 101 |
800 | Control method: 0=Vector, 10=Sensorless Vector, 20=V/f | 0 |
CM Smart Chain Hoist
Pr. | Name | Setting |
---|---|---|
9 | Electronic thermal O/L relay/Rated motor current | 13 |
1 | Maximum frequency | 110 |
3 | Base frequency | 106 |
71 | Applied Motor | 3 |
80 | Motor Capacity (kw) | 2.63 |
81 | Motor Poles | 4 |
83 | Motor Voltage | 230 |
84 | Motor Frequency | 106 |
125 | Terminal 2 gain frequency | 106 |
359 | Motor encoder direction | 100 |
800 | Control method: 0=Vector, 10=Sensorless Vector, 20=V/f | 0 |
820 | Speed control P gain 1 | 10 |
Floorpocket Lift
Pr. | Name | Setting |
---|---|---|
9 | Electronic thermal O/L relay/Rated motor current | 17.5 |
1 | Maximum frequency | 80 |
3 | Base frequency | 60 |
71 | Applied Motor | 3 |
80 | Motor Capacity (kw) | 3.7 |
81 | Motor Poles | 4 |
83 | Motor Voltage | 230 |
84 | Motor Frequency | 60 |
125 | Terminal 2 gain frequency | 60 |
800 | Control method: 0=Vector, 10=Sensorless Vector, 20=V/f | 0 |