Stagehand Pro 2 Parameters

There are a lot of parameters - just 1 mis-set parameter can cause countless hours of troubleshooting chaos.

If you've confirmed the parameters below, aren't seeing a Brake Fault and are feeling stuck, it's time to start from scratch by resetting the VFD back to factory settings. Once you have reset the VFD you'll need to manually input the Stock Parameters.

Set parameter 77 = 2 before jumping into manually entering parameters!

Jump to the bottom of the page to find the proper values for each of our stock machines.

Stagehand Pro 2 Stock Parameters

No.NameNotesSetting value

0

Torque boost

Compensate for low torque in V/f mode

4

1

Maximum frequency

Max frequency output from the VFD

120

2

Minimum frequency

Min frequency output from the VFD

0

3

Base frequency

From motor nameplate

60

7

Acceleration time

Drive level - not used

0

8

Deceleration time

Drive level - not used

0

9

Electronic thermal O/L relay/Rated motor current

From motor nameplate

17.5

10

DC injection brake operation frequency

Hz level when the VFD will apply the DC injection braking

0.5

11

DC injection brake operation time

DC injection brake timing

0.5

12

DC injection brake operation voltage

Voltage applied (% of input voltage)

4

13

Starting frequency

VFD will not start below this value

0.5

22

Stall prevention operation level (torque limit level)

Torque limit (%)

200

30

Regenerative function selection

Brake resistor installed

1

70

Special regenerative brake duty

Based on braking resistor installed

10

71

Applied motor

3 = Induction motor

3

72

PWM frequency selection

Performance & noise

15

73

Analog input selection

+/-10VDC with reversing

14

77

Parameter write selection

enabled across all states

2

79

Operation mode selection

External operation

0

80

Motor capacity

From motor nameplate

3.7

81

Number of motor poles

Nameplate motor RPM 2=3500rpm, 4=1750rpm, 6=1150rpm

4

83

Rated motor voltage

From motor nameplate

230

84

Rated motor frequency

From motor nameplate

60

96

Auto tuning setting/status

0

117

PU communication station number

Modbus

1

118

PU communication speed

Modbus

384

119

PU communication stop bit length / data length

Modbus

0

120

PU communication parity check

Modbus

0

121

Number of PU communication retries

Modbus

1

122

PU communication check time interval

Modbus

9999

125

Terminal 2 frequency setting gain frequency

Set what 100% = in hertz (overspeed)

60

152

Zero current detection level

% of VFD rated current

5

153

Zero current detection time

seconds to detect zero current

0.1

156

Stall prevention operation selection

V/f & Magnetic flux modes only

0

180

RL terminal function selection

I/O

9999

181

RM terminal function selection

I/O

9999

182

RH terminal function selection

I/O

50

183

MRS terminal function selection

I/O

9999

184

RES terminal function selection

I/O

9999

190

RUN terminal function selection

I/O

199

191

SU terminal function selection

I/O

9999

192

IPF terminal function selection

I/O

9999

193

OL terminal function selection

I/O

9999

194

FU terminal function selection

I/O

9999

195

ABC1 terminal function selection

I/O

99

252

Override Bias

old school overspeed

100

285

Overspeed detection frequency (speed deviation excess detection frequency)

too fast

20

316

D03 Output Selection

Y13 Signal: Zero current detection to PLC (keypad or PC)

113

331

RS-485 communication station number

Modbus

1

332

RS-485 communication speed

Modbus

384

333

RS-485 communication stop bit length / data length

Modbus

0

334

RS-485 communication parity check selection

Modbus

0

359

Encoder rotation direction

CW or CCW

1

368

Feedback gain

Drive level PID

1

369

Number of encoder pulses

Motor Encoder resolution (vector mode)

1024

374

Overspeed detection level

Mitsu default

9999

376

Encoder signal loss detection enable/disable selection

Enabled

1

414

PLC function operation selection

PLC program to load (A700=1, A800=2)

1 or 2

539

Modbus Communication check time interval

No communication check (signal loss detection)

9999

549

Protocol selection

MODBUS RTU protocol

1

550

NET mode operation command source selection

The RS-485 terminals are the command source when in the PU

1

800

Control method selection

0=Vector, 10=Sensorless Vector, 20=V/f

0

802

Pre-excitation selection

Servo lock

1

820

Speed control P gain 1

Drive level PID

20

1199

PLC function user parameter 50

open circuit detection

50

C3

Terminal 2 frequency setting bias

C4

Terminal 2 Input Gain

Making sure 100% = 60Hz See the instructions on setting the C4 value.

Stagehand Pro 2 Machine Specific Parameters

Spotline/Pushstick/Revolver

Pr.NameSetting

9

Electronic thermal O/L relay/Rated motor current

13.5

3

Base frequency

60

71

Applied Motor

3

80

Motor Capacity (kw)

3.7

81

Motor Poles

4

83

Motor Voltage

230

84

Motor Frequency

60

125

Terminal 2 gain frequency

60

359

Motor encoder direction

1

800

Control method: 0=Vector, 10=Sensorless Vector, 20=V/f

0

CM Smart Chain Hoist

Pr.NameSetting

9

Electronic thermal O/L relay/Rated motor current

13

1

Maximum frequency

110

3

Base frequency

106

71

Applied Motor

3

80

Motor Capacity (kw)

2.63

81

Motor Poles

4

83

Motor Voltage

230

84

Motor Frequency

106

125

Terminal 2 gain frequency

106

359

Motor encoder direction

0

800

Control method: 0=Vector, 10=Sensorless Vector, 20=V/f

0

Floorpocket Lift

Pr.NameSetting

9

Electronic thermal O/L relay/Rated motor current

17.5

1

Maximum frequency

80

3

Base frequency

60

71

Applied Motor

3

80

Motor Capacity (kw)

3.7

81

Motor Poles

4

83

Motor Voltage

230

84

Motor Frequency

60

125

Terminal 2 gain frequency

60

800

Control method: 0=Vector, 10=Sensorless Vector, 20=V/f

0