Pro+ Parameters
If after setting the following parameters and you are still having trouble, it's probably a good time to reset the VFD back to factory settings and start fresh.
Set Parameter 77 = 2 before jumping into manually entering parameters!
No. | Name | A800 Values | A700 Values |
---|---|---|---|
0 | Torque boost | 4 | - |
1 | Maximum frequency | 120 | 120 |
2 | Minimum frequency | 0 | 0 |
3 | Base frequency | 60 | 60 |
7 | Acceleration time | 0.1 | .1 |
8 | Deceleration time | 0.1 | .1 |
9 | Electronic thermal O/L relay/Rated motor current | 17.5 | 17.5 |
10 | DC injection brake operation frequency | 0.5 | .5 |
11 | DC injection brake operation time | 0.5 | .5 |
12 | DC injection brake operation voltage | 4 | 4 |
13 | Starting frequency | 0.2 | 0.2 |
22 | Stall prevention operation level (torque limit level) | 200 | 200 |
30 | Regenerative function selection | 1 | 1 |
70 | Special regenerative brake duty | 10 | 10 |
71 | Applied motor | 3 | 3 |
72 | PWM frequency selection | 15 | 15 |
73 | Analog input selection | 1 | 1 |
77 | Parameter write selection | 2 | 2 |
79 | Operation mode selection | 2 | 2 |
80 | Motor capacity | 3.7 | 3.7 |
81 | Number of motor poles | 4 | 4 |
83 | Rated motor voltage | 230 | 230 |
84 | Rated motor frequency | 60 | 60 |
96 | Auto tuning setting/status | 0 | 0 |
117 | PU communication station number | 1 | 1 |
118 | PU communication speed | 384 | 384 |
119 | PU communication stop bit length / data length | 0 | 0 |
120 | PU communication parity check | 0 | 0 |
121 | Number of PU communication retries | 1 | 1 |
122 | PU communication check time interval | 9999 | 9999 |
125 | Terminal 2 frequency setting gain frequency | 60 | 60 |
145 | PU display language selection | 1 | 1 |
152 | Zero current detection level | 5 | 5 |
153 | Zero current detection time | 0.1 | 0.1 |
180 | RL terminal function selection | 9999 | 9999 |
181 | RM terminal function selection | 9999 | 9999 |
182 | RH terminal function selection | 50 | 50 |
187 | MRS terminal function selection | 9999 | 9999 |
189 | RES terminal function selection | 9999 | 9999 |
190 | RUN terminal function selection | 9999 | 9999 |
192 | IPF terminal function selection | 2 | 2 |
194 | FU terminal function selection | 9999 | 9999 |
195 | ABC1 terminal function selection | 199 | 199 |
252 | Override Bias | 100 | 100 |
316 | D03 Output Selection Keypad programmable only | 113 | - |
331 | RS-485 communication station number | 1 | 1 |
332 | RS-485 communication speed | 384 | 384 |
333 | RS-485 communication stop bit length / data length | 0 | 0 |
334 | RS-485 communication parity check selection | 0 | 0 |
359 | Encoder rotation direction | 1 | 1 |
369 | Number of encoder pulses | 1024 | 1024 |
374 | Overspeed detection level | 9999 | 9999 |
376 | Encoder signal loss detection | 1 | 1 |
414 | PLC function operation | 2 | 1 |
549 | Protocol selection | 1 | 1 |
550 | NET mode operation command source selection | 1 | 1 |
800 | Control method selection | 0 | 0 |
820 | Speed control P gain 1 | 20 | 20 |
1199 | PLC function user parameter 50 | 50 | - |
C3 | Terminal 2 frequency setting bias See the instructions on setting the C3 value. | ||
C4 | Terminal 2 Input gain See the instructions on. |