Stagehand Apprentice
There are a lot of parameters - just 1 mis-set parameter can cause countless hours of troubleshooting chaos.
The Stagehand Apprentice does not include an external keypad to the Mitsubishi D700 series VFD. If you need to manually restore parameters, you'll need to open the top of the case to get to the keypad.
With the case open, confirm the stock parameters are set properly, making any adjustments based on the machine connected. If you've checked the parameters and are still stuck, it's time to start from scratch by resetting the VFD back to factory settings.
Once you have reset the VFD you'll need to manually input the Stock Parameters.
No. | Name | Description | 5HP |
---|---|---|---|
1 | Maximum frequency | max output frequency | 120 |
7 | Acceleration time | 0 seconds | 0 |
8 | Deceleration time | 0 seconds | 0 |
9 | Electronic thermal O/L relay | Nameplate FLA Rating | 16 |
13 | Starting frequency | Motor won’t start until the speed signal is at least this value. | 0.5 |
30 | Regenerative function selection | External brake resistor, L1/L2/L3 power source | 1 |
70 | Special regenerative brake duty | duty cycle of the braking resistor | 10 |
71 | Applied motor | Other mfg. standard motor | 3 |
72 | PWM frequency selection | Reduces output noise | 15 |
73 | Analog input selection | 0-5vdc Speed Signal | 1 |
77 | Parameter write selection | Allow parameter writes regardless of operation status. | 2 |
79 | Operation mode selection | Keypad disabled, external control | 0 |
80 | Motor capacity | Motor nameplate kilowatt rating | 3.7 |
83 | Rated motor voltage | Nameplate motor voltage | 230 |
84 | Rated motor frequency | Nameplate frequency | 60 |
96 | Auto tuning setting/status | See Stagehand Apprentice manual for auto-tuning procedure | 0 |
117 | PU communication station number | RS485 Communication | 1 |
118 | PU communication speed | 4800bps | 384 |
119 | PU communication stop bit length | data length: 8 bits, stop bit: 1 bit | 0 |
120 | PU communication parity check | with odd parity check | 0 |
122 | PU communication check time interval | No communication check (default) | 9999 |
125 | Terminal 2 frequency setting gain frequency | Overspeed the drive output | 60 |
190 | RUN terminal function selection | Alarm signal, normally on shuts off if there's a fault | 199 |
192 | A,B,C terminal function selection | general output (used by PLC for motor brake) | 0 |
197 | SO terminal function selection | General output | 180 |
338 | Communication operation command source | RS485 Communication | 0 |
339 | Communication speed command source | RS485 Communication | 0 |
340 | Communication startup mode selection | RS485 Communication | 0 |
549 | Protocol selection | RS485 Communication | 1 |
551 | PU mode operation command source selection | Command source selection | 9999 |
C3 | Terminal 2 frequency setting bias | Making 0% = 0Hz See the instructions on setting the C3 value. | |
C4 | Terminal 2 frequency setting gain frequency | C4 - Enter the value on the Stagehand cabinet or check out the guide |