Drive Communication: Setting VFD Parameters
Use the tabs below for instructions on updating your Drive Communication VFD Parameters
On the VFD Keypad:

Press
until P.0 is displayed
Use the scroll wheel
to select each parameter to set
For Drive Communication, scroll to parameter 118
Press the
button and change the value to 384 with the wheel
Once you are set to the correct value, press
-- the display will flash between the parameter number and the new value.
Use the wheel
to scroll to the next parameter
For Drive Communication, scroll to parameter 332
Press the
button and change the value to 384 with the wheel
Repeat the steps above and make sure all the parameters listed below are set to the correct value too.
Lastly, cycle power to your Stagehand
Drive Communication VFD Parameter Values
Parameters for compatibility with Spikemark 5
Parameter
Description
Pro
Apprentice
79
Operation mode selection
0
0
117
PU communication station number
1
1
118
PU communication speed
384
384
119
PU communication stop bit length
0
0
120
PU communication parity check
0
0
331
RS-485 communication station number
1
N/A
332
RS-485 communication speed
384
N/A
334
RS-485 communication parity check selection
0
N/A
338
Communication operation command source
0
0
339
Communication speed command source
0
0
340
Communication startup mode selection
0
0
549
Protocol selection
1
1
550
NET mode operation command source selection
1
1
551
PU mode operation command source selection
9999
9999