Specifications
Electrical Specifications
Description | Value |
Input Voltage | 200VAC-240VAC 50/60Hz 3P or 1P (single-phase input derates output power by 50%) |
Max Input Current | 30 amps. Supply proper branch circuit protection using UL Class T fuses or a Listed UL 489 Molded Case Circuit Breaker (MCCB) with a maximum allowable rating of 30A. |
Motor Output Voltage | 230VAC 0.2Hz-60Hz |
Max Motor Output Power | 5HP Normal Duty |
Min Motor Output Power | 2HP *Adjust Mitsubishi VFD parameter 9 to reflect motor current rating. **Lower HP possible but auto-tuning is ineffective below 2HP |
Minimum Motor Speed | .5Hz |
Maximum Motor Speed | 60Hz – 400Hz (make sure you do not exceed the rating of your motor) |
Motor Brake Output Voltage | 200VAC-240VAC 50/60Hz |
Motor Brake Output Current | 5A max |
Limit Switch Voltage | 24VDC |
Limit Switch Current | 10mA |
Limit Switch Contact Type | Normally Closed (N.C.) dry contact |
Physical Specifications
Default Mitsubishi Parameters
Parameter Code | Description | Value | Description |
1 | Maximum Frequency | 120Hz | max output frequency |
6 | Low speed Frequency | 5Hz | |
7 | Acceleration time | 2 | seconds |
8 | Deceleration time | 2 | seconds |
9 | Motor full load amps | 16 | |
13 | Starting frequency | 0.5 | Motor won’t start until the speed signal is at least this value. |
30 | Regenerative function | 1 | External brake resistor, L1/L2/L3 power source |
70 | Regenerative brake duty | 10% | duty cycle of the braking resistor |
71 | Motor type | 3 | Other mfg. standard motor |
72 | Carrier frequency | 15 | Reduces output noise |
73 | Analog input selection | 1 | Terminal 2 input 0 to 5V without reversing |
77 | Parameter write selection | 2 | allow parameter writes regardless of status ****SET THIS ONE FIRST*** |
79 | Control mode | 2 | Keypad disabled, external control |
80 | Motor capacity | 3.7 | kilowatts |
83 | Motor voltage | 230V | |
84 | Motor rated frequency | 60Hz | |
125 | Terminal 2 frequency setting gain frequency | 60Hz | *** Max frequency (adjust for overspeed) *** |
180 | RL input terminal | 0 | low-speed operation (default) |
181 | RM input terminal | 62 | inverter reset |
190 | RUN output | 0 | Running |
192 | Relay output | 199 | Fault output (normally closed, opens if fault) |
197 | SO terminal | 180 | Safe Stop output (normally closed, opens if stopped) |